PWV series pressure controlled water valves are usually installed on the inlet of condenser, which can regulate the flow of cooling water according to the change of condensing pressure. When condensing pressure of compressor rises, valve is turned up automatically, so more cooling water enters the condenser to accelerate the condensing of refrigerant. Reversely, when condensing pressure of compressor drops, valve is turned down automatically, so cooling water reduces and the condensing pressure is kept within certain range. Adjust screw rod at clockwise rotation, the valve is turned down; inversely, the valve is turned up.
Type & data
|
Symbol |
Model |
Condenser side |
Liquid side |
Factory setting opening pressure (MPa) |
Kv value m3/h |
|
Refrigerant |
Adjusting range (MPa) |
Max. working pressure (MPa) |
Max. testing pressure (MPa) |
Media |
Max. working pressure (MPa) |
Max. Media temp. (℃) |
|
Low pressure |
PWV3/8 |
R134a, R22,R407C R404A/507 |
0.5→1.8 |
2 |
2.4 |
Fresh water |
1 |
60 |
0.75 |
0.8 |
|
PWV1/2 |
2.5 |
|
PWV3/4 |
3.2 |
|
PWV1 |
5.0 |
|
High pressure |
PWV3/8G |
0.7→2.3 |
2.6 |
3 |
2 |
0.8 |
|
PWV1/2G |
2.5 |
|
PWV3/4G |
3.2 |
|
PWV1G |
5.0 |
|
Kv value is the flow of water in m3/h at a pressure drop across valve of 0.1 MPa,ρ= 1000 kg/m3. |
Connection
|
Model |
Condenser side |
Liquid side |
|
PWV3/8、PWV3/8G |
1/4 flare 7/16"-20UNF nut |
3/8" flare |
|
PWV1/2、PWV1/2G |
1/4 flare 7/16"-20UNF nut |
G1/2 |
|
PWV3/4、PWV3/4G |
1/4 flare 7/16"-20UNF nut |
G3/4 |
|
PWV1、PWV1G |
1/4 flare 7/16"-20UNF nut |
G1 |
|