T series temperature control is a temperature-controlled electric switch, can be directly connected to single-phrase A.C. motors of up to about 1KW, or installed in the control current circuit of D.C. motors and large A.C. motors. T series temperature control has a single pole double throw (SPDT) changeover switch. The position of switch depends on temperature control setting and bulb temperature.
Technical data Ambient temperature -20 ~ 50℃ Cable connection The cable entry can be used for 15mm dia.
Electrical data
|
Voltage |
Non-inductive current |
Inductive current |
|
Full load |
Starting |
|
A.C.110V |
24A |
24A |
144A |
|
A.C.220V |
16A |
16A |
96A |
Type & data
|
Model |
Adjusting range (℃) |
Differential (℃) |
Factory set (℃) |
Max. bulb temperature (℃) |
Bulb size(mm) |
Use condition (℃) |
Capillary tube length (m) |
|
Min. |
Max. |
On |
Off |
Length |
Diameter |
|
T70 |
-70→-35 |
Low 5 High 3 |
15 |
-50 |
-45 |
45 |
80 |
10 |
Ts>Tb |
1.5 |
|
T30 |
-30→0 |
-19 |
-14 |
|
T15 |
-15→15 |
-5 |
0 |
|
T40 |
0→40 |
5 |
20 |
17 |
20 |
70 |
120 |
12 |
Ts<Tb |
|
T90 |
40→90 |
60 |
60 |
120 |
|
T120 |
70→120 |
90 |
95 |
130 | Notes: Ts---bulk temperature, Tb---thermo bulb temperature
|